Trade supplier of HVAC zoning, controls and air distribution components across Australia
AUSTRA SUPPLY
F03 damper actuator, angled view
F03 damper actuator, angled viewF03 damper actuator, front view showing the drive shaft

Zoning and controls · Actuators

F03 damper actuator, 24 VAC

Part number: AS-ACT-F03-24

A compact actuator for motorised zone dampers. It can stop and hold at any point between open and closed, so each zone gets the right amount of air. Slow 1 RPM travel keeps it quiet and easy on the damper.

Supply voltage24 VAC ±10%, 50 Hz
Running torque3.9 N·m (40 kgf·cm) minimum
Output speed1 RPM (90° in about 15 s)
Control3-wire floating, holds any position
Fully documentedDatasheet, drawing and wiring diagram.
Sold as a motor kitWith cable, shaft adapter and gaskets.

Overview

Most damper motors can only open or close. The F03 uses 3-wire floating control, so it stops wherever the control signal stops. This lets a zone run part open, which balances airflow between rooms and reduces noise at the grille.

It delivers 3.9 N·m of running torque, which is enough to turn stiff or older dampers. At 1 RPM it takes about 15 seconds to travel 90°. Slow, even movement is quieter and puts less load on the damper blade.

The F03 works with all three of our zone controllers. It connects with a single six-core cable and a standard RJ11 plug, so no terminal wiring is needed at the actuator.

Typical applications

  • Ducted zoning in homes and apartments
  • Offices and small retail fit-outs
  • Adding zones to an existing system
  • Replacing open/close damper motors

Part numbers

Choose a quantity and add each part to your quote list. Prices are sent by written quote.

Part numberDescriptionSize (mm)MaterialUnitQuote
AS-ACT-F03-24F03 damper actuator, 24 VAC72 × 120 × 62 mmGreen housingEach

Specifications

Electrical

Operating voltage24 VAC ±10%, 50 Hz
No-load current0.25 A maximum
No-load power5 W maximum
Rated capacitor10 µF
Insulation classClass E
Insulation resistance100 MΩ minimum
Dielectric strength500 VAC, 50 Hz, 1 second

Mechanical

Output speed1 RPM
RotationClockwise and counter-clockwise, 90° travel
Running torque3.9 N·m (40 kgf·cm) minimum
Start torque3.9 N·m (40 kgf·cm) minimum
Stall torque4.4 N·m (45 kgf·cm) maximum
Output shaft6 × 6 mm square
Axial play0.5 mm maximum
Backlash (no load)5° maximum

Physical and connection

Dimensions (W × H × D)72 × 120 × 62 mm, including mounting lugs
Noise at 1 m45 dB(A) maximum
ConnectorRJ11 6P6C socket
Control signal3-wire floating: open, neutral, close
Housing colourGreen

Environment

Operating temperature−10 °C to +45 °C
Operating humidity10 to 90% RH, non-condensing

Torque values measured at rated voltage and 25 °C. Specifications may change without notice.

Dimensions

All dimensions in millimetres. Allow clearance on the right-hand side for the RJ11 plug and cable.

Front Side Shaft (open position) 72 106 120 62 90° 6 × 6 mm

Wiring

Connect each actuator to one zone channel on the controller. Power the controller from the 240 V to 24 V transformer.

PowerTransformer240 VAC in, 24 VAC out
ControlZone controllerOne output channel per zone
CableSix-core motor cable15 m standard, 20 m maximum
ActuatorF03RJ11 6P6C socket

Control signals

OpenDrives the damper toward fully open
NeutralCommon return
CloseDrives the damper toward fully closed

Installation notes

  • The 240 V side of the transformer must be connected by a licensed electrician.
  • Connect one actuator per controller channel. Do not share a channel between two motors.
  • Do not turn the coupling or damper blade by hand to test the actuator.
  • If the damper runs in reverse, swap the open and close wires.

Compatible products

Products that are often specified with the f03 damper actuator.

Frequently asked questions

Will the F03 fit my existing dampers?

The F03 has a 6 × 6 mm square output shaft. Use our shaft adapter kit to couple it to the damper spindle. Spindle sizes vary, so check yours before you order.

Can the F03 hold a damper part open?

Yes. With 3-wire floating control the actuator stops wherever the signal stops. Paired with our 4-zone modulating controller, each zone can be set to 25, 50, 75 or 100% open.

What happens if the damper turns the wrong way?

Swap the open and close wires at the actuator. If the blade position is still wrong, remove the actuator and re-align the damper blade.

Which zone controller should I use?

Choose the 4-zone modulating controller if you want each zone to run part open. For simple open/close zoning, use the 4-zone or 6-zone open/close controller. The F03 works with all three.

Need pricing for a project?

Not sure which part you need? Send us the job or your schedule. We will work out the parts list and quote every line.